QOR output forced to 1 (5 wired, 8 required) in FC 36 Module 1,01,02 Block 1001
A QOR output has been forced to 1. The message is intended to encourage documentation of forced logic.
A QOR block functions in such a way that if the value of S10 is 0, then the output is 1 if the number of logic 1 inputs is greater than or equal to the value of S9. With the value of S9 at 0 as well, the number of input 1's will always be greater than or equal to 0. therefore the output value of the block will always be 1.
This message reports system information that is otherwise difficult or impossible to find.